Standard Solution: 10/0.4 kV Package Transformer Substation with Low-Voltage Switchgear — Diagrams, Questionnaires (PDF/DWG)
Standard solution for a 10/0.4 kV package transformer substation with low-voltage switchgear (RUNN): single-line diagrams for 400 and 630 kVA, questionnaires, an overall dimension drawing. PDF is open access, the DWG package is available on request.
Published: 11.06.2026 · Author: engineering department of LK Energy LLC
A ready-made set of drawings for the standard solution of a 10/0.4 kV package transformer substation (KTP) with low-voltage switchgear (RUNN) in two designs — pole-mounted KTPM-400 kVA and urban-type KTPGS-630 kVA: 8 PDF files (8 sheets) — single-line diagrams of the RUNN cabinet with parts lists, order questionnaires, an overall layout drawing, an outdoor lighting cabinet diagram, plus an equipment layout plan and an assembly drawing of the ShchO-90 panel frame (low-voltage switchgear and control panel) for the KTPGS-1000. The drawings were produced by LK Energy engineers based on real production orders (2022). PDFs are freely available below; the DWG package is provided free of charge on request via the form.
What a package substation with LV switchgear is and when it is used
A 10/0.4 kV package transformer substation (KTP) is a fully factory-assembled substation that receives electricity at 10 kV, steps it down to 0.4 kV via a power transformer, and distributes it to consumers. Structurally, a KTP consists of three units: a high-voltage switchgear unit (RUVN) with power fuses, a power transformer (a TMG unit in this solution), and a low-voltage switchgear unit (RUNN). The RUNN is a 0.4 kV cabinet with an incoming switching device, outgoing-line circuit breakers, current transformers, and a commercial metering unit.
By design, a distinction is made between pole-mounted KTPM substations — mounted on a support structure with an outdoor RUNN cabinet — and urban-type KTPGS substations, housed in a metal enclosure with separate compartments for the 10 kV switchgear, the transformer, and the 0.4 kV switchgear. Both designs are included in this package.
The solution addresses a typical task for an outdoor power supply designer: a single-line diagram of the KTP on the 0.4 kV side with an equipment list, an order questionnaire form for the substation manufacturer, and an overall dimension drawing for the site plan. It is used when connecting new consumers to 10 kV networks — residential developments, municipal and agricultural facilities — and when reconstructing worn-out transformer substations. The composition of outgoing lines and the transformer rating are adapted based on the questionnaire.
Technical parameters of the solution
Design 1 — KTPM-400 kVA 10/0.4 U1 (pole-mounted), 2022 drawing.
- Power transformer: TMG-400, 10/0.4 kV, D/Yn-11 connection scheme
- RUNN: 380 V, busbars 630 A (AD31 8x40), PEN AD31 5x50
- Input: NM8S-630S 630A 3P circuit breaker + RE19-41-311500 1000A disconnect switch
- Outgoing lines: 6 × VA-73 160A 3P (5 lines SIP5 4x120 + one spare)
- Metering: T-0.66-1 500/5 accuracy class 0.5S current transformers (6 pcs.), GAMA G3B.147.240 meter + MCL 5.10 modem (supplied by the customer), VCF multimeter
- Surge arresters: OPNp-0.38/0.45/10/2 UKhL1 (0.4 kV), OPNp-10/12 (10 kV)
- RUVN: PT 012-10-50 31.5 U1 power fuses (rated current 50 A, breaking capacity 31.5 kA)
Design 2 — KTPGS-630 kVA 10/0.4 U1 (urban type), 2022 drawing.
- Power transformer: TMG-630 EKO, 10/0.4 kV, Y/Yn-0 connection scheme
- RUNN: 380 V, busbars 1000 A (AD31 10x60), PEN AD31 10x60
- Input: RPB-10 1000A disconnect switch with 1000A fuses
- Outgoing lines: 6 × NM8S-250S (160 A — 3 pcs., 250 A — 2 pcs., 100 A — 1 pc.)
- Metering: T-0.66 1200/5 accuracy class 0.5S current transformers (3 pcs.), GAMA G3B meter in a separate KDE-U metering cabinet (sealable)
- Outdoor lighting cabinet: RD 25-40 230V contactor with manual control, SOU-1 230V AC dusk-to-dawn relay
- Layout: separate compartments for 10 kV switchgear / transformer / 0.4 kV switchgear, plan dimensions 3000×2350 mm
- RUVN: PT 012-10-63 31.5 U3 power fuses (rated current 63 A, breaking capacity 31.5 kA)
The remaining parameters of a specific design (transformer rating, outgoing-line ratings, lighting, ventilation, alarm system, climate design) are agreed upon via the questionnaire.
2022 drawings: main inscriptions are in Ukrainian; some designations and table headers are in Russian.
Package contents and downloads
| No. | Document | Purpose | Sheets | File |
|---|---|---|---|---|
| 1 | Schematic electrical diagram of the RUNN cabinet — KTPM-400 kVA | 0.4 kV single-line diagram with a parts list | 1 | |
| 2 | Questionnaire for KTPM-400 kVA 10/0.4 U1 | Order form: RUVN, transformer, RUNN panel | 1 | |
| 3 | Schematic electrical diagram of the RUNN cabinet — KTPGS-630 kVA | 0.4 kV single-line diagram with a parts list | 1 | |
| 4 | Questionnaire for KTPGS-630 kVA 10/0.4 U1 | Order form: RUVN, transformer, RUNN panel | 1 | |
| 5 | Overall layout drawing of the KTPGS | Top view, elevations A/B/C, compartment layout | 1 | |
| 6 | Outdoor lighting cabinet diagram | Lighting control circuits with a dusk-to-dawn relay | 1 | |
| 7 | Equipment layout plan (KTPGS-1000) | 10 kV switchgear, transformer compartment, 0.4 kV switchgear; plan dimensions 3600×2600 mm | 1 | |
| 8 | Assembly drawing of the ShchO-90 panel frame (KTPGS-1000) | Base frame of the 0.4 kV low-voltage switchgear and control assembly within the KTPGS | 1 |
The heading of the original questionnaire form contains a typo, "KTPM-250"; based on the stamp and the transformer, the design is 400 kVA.
For the KTPGS-1000, the following are additionally available: an equipment layout plan and an assembly drawing of the ShchO-90 panel frame.
Drawing previews
DWG package on request
We will send the full DWG models of both designs (RUNN diagram + questionnaire + overall dimension drawing in a single AutoCAD file) to your email free of charge.
Frequently asked questions
Can these diagrams be used in a working project?
Yes — as a standard base solution. Site-specific adaptation, load calculation, and verification of compliance with the current PUE (electrical installation rules) and DSTU (Ukrainian national standards) are the designer's responsibility. The drawings were made based on real LK Energy production orders from 2022.
What equipment is specified in the diagrams?
NM8S (250S/630S) and VA-73 circuit breakers, RPB-10 and RE19-41 disconnect switches, T-0.66 accuracy class 0.5S current transformers, a GAMA G3B meter with an MCL modem, OPNp surge arresters, BKN modular devices. Designs using other equipment are agreed upon via the questionnaire.
How can I get the DWG files?
Fill out the form on this page — we will send the DWG package to your email within one business day.
Does LK Energy manufacture KTPs to these diagrams?
Yes. We manufacture KTPs (both pole-mounted and urban type), RUNN cabinets, KSO/KRU switchgear cubicles (cable and complete switchgear units), and ShchO-90 panels (low-voltage switchgear and control panels) at our own production facility in Odesa — more than 3,000 units of equipment have been manufactured since 2015.
Will you help adapt the solution to my facility?
Yes, we advise designers on selecting the transformer rating, equipment ratings, and completing the questionnaire: +38 067 104 94 91.
The diagrams are provided as a reference standard solution. Site-specific adaptation, verification of protective device selectivity, and compliance with current standards (PUE, DSTU, DBN — state building codes) are the designer's responsibility. LK Energy is not liable for the use of this solution without adaptation to the conditions of a specific facility.
Any questions left?
Write or call us — we answer to the point. Preliminary reply within 24 hours.
+380 67 104 94 91